Blog

How Can the Starting Current in Motors be Reduced?

We use cookies to enhance your experience. By continuing to browse this site you agree to our use of cookies. More info.

Scientists from the University of Kwazulu-Natal, the University of Witwatersrand, and Icarus Avionics in South Africa have collaborated on a new paper published online in the journal Energies investigating strategies for reducing the starting current in motors. Vsi Fed Synchronous Motor Drive

How Can the Starting Current in Motors be Reduced?

Study: Reduction of Starting Current in Large Induction Motors . Image Credit: AMatveev/Shutterstock.com

High inrush and run-up currents during starting is a challenge when designing large induction motors. High start-up currents can cause problems such as voltage dipping below acceptable levels and system stability issues in weak supplies. Capacity can be pulled down below the maximum levels in islanded systems.

Excessive current can be drawn during switch-on surges. Unnecessary tripping can occur in protection relays, other connected components can malfunction, and weak grids can become destabilized. Large inrush currents occur in several devices such as induction motors and transformers. Moreover, surges occur in large electromagnetic devices when they are switched on to induce the magnetic field.

In directly connected induction motors, a magnetic field is formed when voltage is applied on start-up. After this initial magnetization surge, a high run-up current occurs. When machines are running up to speed, between five and ten times the full-load current can be drawn. If this is not mitigated, overloading can occur in extreme cases, leading to the system tripping.

DSTATCOM induction motor starting. Image Credit: Habyarimana, M et al., Energies

Induction motors are analogous to transformers. Because they are electromagnetic devices, induction motors draw both active and reactive power. If there is a high inductive loading, this can lead to power quality issues. One common strategy to mitigate poor power factors is to use capacitor compensation. This is achieved by connecting parallel capacitors to compensate for power loads.

Using capacitors is not a new practice. For decades, they have been utilized in single-phase induction motors. When in series with auxiliary winding, capacitors can be used during both start-up and when the device is running. Studies have reported boosted starting voltage outputs using electronic control both in parallel and in series. However, potential over-voltage can be caused, which has implications for system performance.

Parallel capacitor compensation during start-up has not been widely investigated in the current literature. Large induction motors are extremely inductive during start-up, and supplying reactive power to these systems may be more effective than supplying energy from the grid.

Possible filter arrangements—low pass filter most suitable in this application. Image Credit: Habyarimana, M et al., Energies

The paper in Energies has evaluated the use of parallel capacitors for reducing starting currents in induction motors. Several motors of increasing size have been assessed for their compensation requirements in terms of reactive power requirements during start-up.

The authors have highlighted that inverters can be used in smaller devices, converting them to variable speed drives and reducing the starting current. Unfortunately, this strategy can be too expensive for larger induction motors.

Increasing complexity and power demands leads to rapidly increasing costs that do not correlate with power ratings in a linear fashion, making them prohibitive for devices that operate in megawatts. The dominance of reactive power absorption in larger induction motor starting cycles means it is possible to compensate for starting currents using capacitors that generate reactive power.

Private discussions with an electrical contractor highlighted the practical problem of temporary voltage drops caused by sudden high currents during start-up in induction motors in large systems such as air-conditioning fans, water pumping stations, and motors at the end of long feed lines. The problem occurs not just at motor terminals, but over the entire power bus which feeds the starter motor.

Results of the author’s investigation of several induction motors demonstrated that as they become larger, they become more inductive. Simulations were employed to analyze the current reduction capabilities of connecting capacitors to these systems.

To test the concept, the authors employed a small experimental motor during their experiments. To increase its induction and mimic a much larger system, several series inductors were incorporated into the test system. The research’s proposed method was confirmed using experimental analysis.

Complete system power circuit. Image Credit: Habyarimana, M et al., Energies

Reducing the harmonics of systems was also investigated in the research. Systems can be susceptible to low-frequency harmonics, requiring the use of filters. The authors proposed using in-line inductors in conjunction with capacitors. It was demonstrated experimentally that this considerably reduced run-up current harmonics, in line with simulations.

Another strategy explored in the paper was point-on switching. It was demonstrated that utilizing this approach reduces transient effects during turn-on. This method possesses the advantage of allowing soft connection of equipment.

The authors have stated that future work will investigate the possibility of constructing commercial devices which possess full capacitor turn-on and turn-off capabilities.

Habyarimana, M, Dorrell, D.G & Musumpuka, R (2022) Reduction of Starting Current in Large Induction Motors Energies 15(10) 3848 [online] mdpi.com. Available at: https://www.mdpi.com/1996-1073/15/10/3848

Disclaimer: The views expressed here are those of the author expressed in their private capacity and do not necessarily represent the views of AZoM.com Limited T/A AZoNetwork the owner and operator of this website. This disclaimer forms part of the Terms and conditions of use of this website.

Reg Davey is a freelance copywriter and editor based in Nottingham in the United Kingdom. Writing for AZoNetwork represents the coming together of various interests and fields he has been interested and involved in over the years, including Microbiology, Biomedical Sciences, and Environmental Science.

Please use one of the following formats to cite this article in your essay, paper or report:

Davey, Reginald. (2022, May 25). How Can the Starting Current in Motors be Reduced?. AZoM. Retrieved on October 18, 2023 from https://www.azom.com/news.aspx?newsID=59153.

Davey, Reginald. "How Can the Starting Current in Motors be Reduced?". AZoM. 18 October 2023. <https://www.azom.com/news.aspx?newsID=59153>.

Davey, Reginald. "How Can the Starting Current in Motors be Reduced?". AZoM. https://www.azom.com/news.aspx?newsID=59153. (accessed October 18, 2023).

Davey, Reginald. 2022. How Can the Starting Current in Motors be Reduced?. AZoM, viewed 18 October 2023, https://www.azom.com/news.aspx?newsID=59153.

Do you have a review, update or anything you would like to add to this news story?

In this interview, AZoM speaks to LECO's Andrew Storey about glow discharge spectrometry and the opportunities offered by LECO's GDS950.

At the Advanced Materials Show 2023, AZoM sat down with Tom Warwick, Director and one of the two Founders of Blue Scientific, to discuss the rapid growth of the business and its ambitions for the future.

Phil Levesque & Charlie Pryor

In this interview, AZoM speaks to Instron's Phil Levesque and Charles Pryor about the importance of mechanical testing for electric vehicle batteries.

The DynaPro Zetastar Static Light Scattering Detector performs simultaneous dynamic and static light scattering or dynamic and electrophoretic light scattering (DLS/SLS/ELS) measurements all within one instrument.

The Thermo Scientific™ ARL iSpark™ Plus Series OES Metal Analyzer is the perfect instrument for every process from routine elemental analysis to heavy-duty metals R&D.

Sorbent Technologies offers a wide range of custom column packing services thanks to a large portfolio of chemistries and column configurations.

The global semiconductor market has entered an exciting period. Demand for chip technology is both driving the industry as well as hindering it, with current chip shortages predicted to last for some time. Current trends will likely shape the future of the industry, which is set to continue to show

The primary distinction between graphene-based batteries and solid-state batteries lies in the composition of either electrode. Although the cathode is commonly changed, carbon allotropes can also be employed in fabricating anodes.

In recent years, the IoT is rapidly being introduced into almost all sectors, but it has particular importance in the EV industry.

AZoM.com - An AZoNetwork Site

How Can the Starting Current in Motors be Reduced?

7.5 Hp Motor Amps 3 Phase Owned and operated by AZoNetwork, © 2000-2023